Add APC UPS & ZFS exporter (#331)

* add apcupsd_exporter rules

* add zfs_exporter rules
This commit is contained in:
Yannick Markus 2023-02-12 20:01:26 +01:00 committed by GitHub
parent 7e53aa2edd
commit 7aeccf2874
No known key found for this signature in database
GPG key ID: 4AEE18F83AFDEB23

View file

@ -2089,6 +2089,30 @@ groups:
query: 'node_zfs_zpool_state{state!="online"} > 0'
severity: critical
for: 1m
- name: ZFS exporter
slug: zfs_exporter
doc_url: https://github.com/pdf/zfs_exporter
rules:
- name: ZFS pool out of space
description: Disk is almost full (< 10% left)
query: 'zfs_pool_free_bytes * 100 / zfs_pool_size_bytes < 10 and ON (instance, device, mountpoint) zfs_pool_readonly == 0'
severity: warning
- name: ZFS pool unhealthy
description: ZFS pool state is {{ $value }}. See comments for more information.
query: 'zfs_pool_health > 0'
severity: critical
comments: |
0: ONLINE
1: DEGRADED
2: FAULTED
3: OFFLINE
4: UNAVAIL
5: REMOVED
6: SUSPENDED
- name: ZFS collector failed
description: ZFS collector for {{ $labels.instance }} has failed to collect information
query: 'zfs_scrape_collector_success != 1'
severity: warning
- name: OpenEBS
exporters:
@ -2362,3 +2386,35 @@ groups:
* FAILURE 2 false - The build had a fatal error.
* NOT_BUILT 3 false - The module was not built.
* ABORTED 4 false - The build was manually aborted.
- name: APC UPS
exporters:
- name: mdlayher/apcupsd_exporter
slug: apcupsd_exporter
doc_url: https://github.com/mdlayher/apcupsd_exporter
rules:
- name: APC UPS Battery nearly empty
description: Battery is almost empty (< 10% left)
query: 'apcupsd_battery_charge_percent < 10'
severity: critical
- name: APC UPS Less than 15 Minutes of battery time remaining
description: Battery is almost empty (< 15 Minutes remaining)
query: 'apcupsd_battery_time_left_seconds < 900'
severity: critical
- name: APC UPS AC input outage
description: UPS now running on battery (since {{$value | humanizeDuration}})
query: 'apcupsd_battery_time_on_seconds > 0'
severity: warning
- name: APC UPS low battery voltage
description: Battery voltage is lower than nominal (< 95%)
query: '(apcupsd_battery_volts / apcupsd_battery_nominal_volts) < 0.95'
severity: warning
- name: APC UPS high temperature
description: Internal temperature is high ({{$value}}°C)
query: 'apcupsd_internal_temperature_celsius >= 40'
severity: warning
for: 2m
- name: APC UPS high load
description: UPS load is > 80%
query: 'apcupsd_ups_load_percent > 80'
severity: warning