- name: APC UPS
|
||||
exporters:
|
||||
- name: mdlayher/apcupsd_exporter
|
||||
slug: apcupsd_exporter
|
||||
doc_url: https://github.com/mdlayher/apcupsd_exporter
|
||||
rules:
|
||||
- name: APC UPS Battery nearly empty
|
||||
description: Battery is almost empty (< 10% left)
|
||||
query: 'apcupsd_battery_charge_percent < 10'
|
||||
severity: critical
|
||||
- name: APC UPS Less than 15 Minutes of battery time remaining
|
||||
description: Battery is almost empty (< 15 Minutes remaining)
|
||||
query: 'apcupsd_battery_time_left_seconds < 900'
|
||||
severity: critical
|
||||
- name: APC UPS AC input outage
|
||||
description: UPS now running on battery (since {{$value | humanizeDuration}})
|
||||
query: 'apcupsd_battery_time_on_seconds > 0'
|
||||
severity: warning
|
||||
- name: APC UPS low battery voltage
|
||||
description: Battery voltage is lower than nominal (< 95%)
|
||||
query: '(apcupsd_battery_volts / apcupsd_battery_nominal_volts) < 0.95'
|
||||
severity: warning
|
||||
- name: APC UPS high temperature
|
||||
description: Internal temperature is high ({{$value}}°C)
|
||||
query: 'apcupsd_internal_temperature_celsius >= 40'
|
||||
severity: warning
|
||||
for: 2m
|
||||
- name: APC UPS high load
|
||||
description: UPS load is > 80%
|
||||
query: 'apcupsd_ups_load_percent > 80'
|
||||
severity: warning
|
||||
|
|
|
|||